FLOW CONTROL PANEL
A floor standing flow control panel contains all the flow train components. This panel is constructed of 10 gauge sheet steel from the floor to the top of the panel. The panel has an open back for easy maintenance and 12 deep side panels for protection of the components and good appearance.
FITTINGS AND PIPING
Piping is copper and black iron pipe. Fittings are brass flare type NPT fittings for copper piping and NPT iron pipe fittings for the black iron pipe.
NITROGEN FLOW CONTROL
Nitrogen gas line includes manual shut off ball valve, pressure regulator, pressure relief valve, pressure gauge, flowmeter with regulating valve, normally open solenoid for automatic actuation, and check valve.
ENDOTHERMIC GAS FLOW CONTROL
Endothermic gas flow system includes manual shut off valve, pressure gauge, solenoid for automatic shut off, Waukee flowmeter with regulating valve (specifically calibrated for endothermic gas at your inlet pressure), and low flow detection system.
NATURAL GAS OR PROPANE GAS FLOW CONTROL
Natural Gas or propane line includes manual shut off valve, pressure regulator, pressure gauge, solenoid for automatic shut off, flowmeter with regulating valve, and check valve.
BURN OFF
Natural gas fed burn off at exit port does not require flammables to be present for flame to burn. Includes electronic ignition (turned on from control panel). Turns off automatically if flame goes out. Complete gas train with ball valve, solenoid, pressure gauge and adjustment valve. (Can be specified for propane.)
VISUAL INDICATION OF GASES
There are pilot lights which indicate which gases are flowing.
VISUAL AND AUDIBLE ALARMS
A piezo buzzer with pushbutton silencer is provided to indicate any alarm condition. In addition, specific pilot lights indicate precisely which alarm conditions are activated. Silencer does not turn off pilot light indicator. A flashing light is optional.
LOW TEMPERATURE ALARM
The control has a temperature based alarm which is set at 1400F (760C) below which flammables may not be introduced. (See information below on optional low temperature bypass for this alarm.)
ENDOTHERMIC GAS LOW FLOW ALARM
Endothermic gas line has a differential pressure switch and adjustable orifice valve which will indicate low flow condition even at low pressures. There is a delay timer to temporarily bypass the system for start up.
DOOR INTERLOCK ALARM
There is a door interlock switch which prevents flammables from flowing unless the door is closed.
POWER FAILURE
Emergency purge is activated if there is a power failure. (There is a normally open solenoid to do this.) Endothermic gas automatically turns off also.
NITROGEN PURGE CAPABILITY
A pressure switch monitors the ability of the nitrogen to flow in case of an alarm condition. Flammables can not flow without sufficient nitrogen pressure.
LOSS OF BURN OFF FLAME IGNITION SOURCE
Turns off flammables and initiates inert purge.
ATMOSPHERE SAMPLE PORT
An alloy sample port is provided. There is a ball valve to close this off when not in use. This is used to sample the atmosphere for dew point content.
SAFETY REGULATIONS
This atmosphere system is designed to meet or exceed the regulations of the National Fire Protection Agency for controlled atmosphere furnaces (NFPA-86C.)
IRI OR FM APPROVAL
L&L will provide all necessary information to customers insurance carrier for approval purposes.
ATMOSPHERE INSTRUCTIONS
A very complete instruction manual, specifically written for the atmosphere system, is included. This includes theory of operation of all major systems and subsystems, full maintenance instructions and schedules, component lists, component instructions and data sheets, emergency procedures, cautions, and start up and shut down procedures. A complete flow schematic of the atmosphere system is provided.
|